60 Days to Plan Becomes 30 Days to Fix: California's 2027 Tank Law Changes

PASS mascot Richard reaching for the nozzle of a dispenser opened for repair at a California fuel station, palm trees and golden hills behind and a red toolbox at its base, under the title 30 DAYS TO FIX

Through 2026, a California tank inspection report with violations starts a 60-day clock. At the end of it, you owe your local agency a plan.

From January 1, 2027, the clock is 30 days. And at the end of it, you owe the fix.

That is the biggest of three changes in two new state laws, AB 2776 and SB 795. The other two are narrower. One limits where vacuum, pressure or hydrostatic monitoring is required. The other lets E10 vapor recovery equipment be used with E15 until 2029. Here is what each law says. We also flag where the State Water Resources Control Board reads further than the law.

The 30-day clock starts when the report arrives

AB 2776 rewrites Health and Safety Code section 25288(d). The permit holder must "return to compliance within 30 days after receiving" the inspection report. That covers the local agency's compliance report and a special inspector's report.

The clock starts when you receive the report, not on the inspection day. Write down the date each report reaches you.

The law puts this duty on the permit holder. The Water Board's notice says owners and operators. If different companies hold those roles at your site, agree now on who watches the clock.

Need more time? The plan must arrive by day 30

Some fixes take longer than 30 days. A repair can wait on parts or a contractor. The law allows for that. Your local agency "may approve a plan to return to compliance in excess of 30 days."

There is a catch. The agency must receive that plan "within 30 calendar days" of you getting the report. Received, not mailed. Calendar days, so weekends count. And the agency may approve the plan. It does not have to.

So decide early. By about day 20, know whether the fix will be done by day 30. If it won't, send the plan then.

One gray area: a report that arrives late in 2026. Its day 30 can fall in January 2027. We found nothing in the new section that says which clock applies to it. Ask your local agency.

UST Compliance Tools

Beat the Clock

Set how long each step of a repair could take at your site. Then watch the fix race California's old clock and its new one.

The starting numbers are only an example, not typical repair times. Use your own.

7 days
14 days
12 days

Through 2026

The report starts a 60-day clock. Due at the end: a work plan to your local agency, as the Water Board sums up the rule.

Plan due day 60

Day 60: plan

From January 1, 2027

The report starts a 30-day clock. Due by day 30: the fix, or a plan your local agency has received. H&SC 25288(d).

Day 20: decide
Day 30
Day 0Day 60

Day 20: our advice to decide, not the lawA deadline

Your next step

Add it to turn the days into dates. The clock counts from the day you received the report, not the inspection day.

General guidance, not legal advice. Your local agency decides whether to approve a plan for more time. Ask it before you count on one.

Sources: California Health and Safety Code 25288(d), as amended by AB 2776, from January 1, 2027 (waterboards.ca.gov). The rule through 2026 as summed up in the Water Board's notice of October 28, 2026 (notice). Days are calendar days.

Built by PASS Training & Compliance, serving the UST industry with compliance, operator training, and remote tank monitoring. passtesting.com

Vacuum, pressure or hydrostatic monitoring: buried parts only

In California, tanks installed on or after July 1, 2004 have two walls. The space between them must stay under constant vacuum or pressure. Liquid level methods in that space also count. This is VPH monitoring. The goal is to catch a break in either wall before fuel or vapor gets out.

AB 2776 adds three words to section 25290.1(e). The rule now covers the space between the walls of the tank "that is buried."

The Water Board's notice goes one step further. It says unburied product piping will not need VPH monitoring after January 1, 2027. The new words do not mention piping. The Board's reading fits the law's definition of a tank, which includes the pipes connected to it. Still, it is the Board's reading, not words in the law.

If you have unburied piping on VPH now, do not switch anything off on January 1. Ask your local agency first, and get the answer in writing. Buried parts stay under VPH either way.

E15: the equipment maker files the paper, not you

SB 795 adds section 25299.9. It covers enhanced vapor recovery equipment, the systems that capture gasoline vapor at a fuel site. Equipment suitable for E10 is "deemed certified" for blends above 10 and up to 15 percent ethanol. The condition: its maker has filed a statement of compatibility.

The maker signs that statement under penalty of perjury. It goes to the State Air Resources Board, Cal/OSHA, the Division of Measurement Standards and the State Fire Marshal. The Air Resources Board publishes the list of makers who have filed. Section 25299.9 ends on January 1, 2029.

Three things this law does not do:

  • It does not cover the rest of your tank system. The Water Board reminds owners and operators to still show the tank system is compatible with the fuel. Its notice says some parts are rated only to E10 by their makers. It names fiberglass tanks built before 1990, and some piping, turbines and line leak detectors.

  • It does not set the labels. The State Fire Marshal must write label rules for stations that sell the blend. The law set a deadline of December 31, 2026. When we wrote this, we could not find them published.

  • It does not ask you to apply for anything. The Water Board's notice mentions a two-year E15 certification through the State Fire Marshal. We did not find that step in SB 795. The law says the opposite for a station that meets the maker's statement and the label rules. That station needs no new certification from any state agency just for selling the blend. Do not file for one unless the Fire Marshal's office tells you it exists.

For the equipment side of E15, our earlier piece walks through compatibility, risk and best practices.

What to do first

  1. Log the date each inspection report arrives. Day 30 is 30 days after that date.

  2. Name one person to watch the clock. Owner, operator or service company: pick one and write it down.

  3. Line up repair help before your next inspection. Thirty days leaves little room to find a contractor. Service companies, expect calls in the first week after a report, not the sixth.

  4. Decide by about day 20. If the fix won't be done by day 30, send the plan so the agency gets it by day 30.

  5. Keep dated proof of every fix. Repair records and test results show the return to compliance.

  6. Leave VPH on unburied piping alone for now. Change it only with your local agency's written OK.

  7. Before you sell E15, check the paperwork. Get the maker's statement for the vapor recovery equipment. Confirm every tank system part is rated for E15. Follow the Fire Marshal's label rules.

The Bottom Line

From January 1, 2027, a California inspection report gives you 30 days to fix, not 60 days to plan. A longer fix needs a plan the agency receives by day 30. VPH covers the buried tank, and the Water Board says unburied piping drops out. E10 vapor recovery equipment can serve E15 until 2029, once its maker files the statement. Your tank system still has to be compatible. Write down the day each report arrives. Everything else counts from there.

If your California team needs operator training, the PASS Training Marketplace has state operator courses.

Running California sites and not sure how the new clock fits your inspection cycle? Talk to us.

Previous
Previous

Indiana Will Pay Half to Pull an Old Tank. Most of the Money Is Still Unspent.

Next
Next

RCRA at 50: What Five Decades Built Into Your Tank Rules